Regarding greases for outdoor connections: Noalox for general use (not necessarily for aluminum)? Dielectric...











up vote
1
down vote

favorite












I've googled this already and found many people saying that Noalox is only for copper to aluminum connections. I know that Noalox stands for "no aluminium oxidation" but brand names often change meaning from their origins over time. I've also seen people claiming their bottle says it is only for aluminum to copper, while other people say their bottle also says it can be used for copper to copper.



Well, my bottle doesn't say anything about aluminium or copper - it just says it can be used for improving and protecting electrical connections.



Since I am replacing some outdoor outlets and switches that are about 20 years old and mostly rusted to hell, I thought it might be a good idea to put some conductive grease on the contacts for longevity's sake. (I am already replacing all outdoor wingnuts with weatherproof wingnuts which I think also have some kind of grease inside).



It seems Noalox is the only thing my local Home Depot carries for this purpose (or the employee is ill informed) and I'm on a tight schedule so I can't wait for something like Penetrox E-8 to arrive. I know there are concerns about Noalox actually potentially reducing connectivity, but my main concerns is simply ambient humidity and condensation causing corrosion in the contacts over time.



My feeling is that Noalox will do a decent job in this regard, and so even if there is a 1-5% cost in connectivity, there is a 100% improvement in anti-corrosive longevity. Am I wrong? Anyone else care to weigh in?



A related side question: is it a crazy idea to use dielectric grease on the prongs of an outdoor device that is essentially permanently installed and will be plugged into an outdoor receptacle, potentially for years on end? Or is there a better grease for this? Or better nothing at all?



I know there are concerns about non-conductive grease in high voltage applications since they might actually reduce conductivity, but considering most devices are designed for 110V and my mains is actually more like 124V, I don't see that being a huge issue. Especially since these outdoor devices aren't high amperage.










share|improve this question









New contributor




Daniel is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.




















  • Most devices are designed for 125V. Mains voltage hasn't been 110 since the war. When power was first marketed to the masses, it was 110V, and naturally, that stuck the way "Xerox" stuck.
    – Harper
    Dec 4 at 3:36










  • Um, most devices are designed for international use, and 125V is not standard the world over (or even where it is, it's not always dependable). Almost every device I've seen is labeled as 110V - 125V, and sometimes only as 110V. And most devices are built with even more tolerance than the label indicates. Similarly, the other main standard is 220V which actually varies in practice from 220V - 240V+.
    – Daniel
    Dec 4 at 4:12












  • I am discussing the context of your question, which is the I
    – Harper
    Dec 4 at 4:21










  • My point is I'd expect 110V would be well within the design specs / tolerances of any modern device, and I'm doubting that dielectric grease would affect the conductivity by that much. I could be wrong about the effect of the grease - I very much doubt I am wrong about acceptable voltage ranges on any given mainstream electrical device. Mains being reliably 125V in America is pretty irrelevant considering the vast majority of electronic components are built in China for a global market, and even American- or European-built devices will also be aiming for global distribution 9 times of 10.
    – Daniel
    Dec 4 at 4:25












  • I'm just trying to say voltage is supposed to be 120V not 110V, so it's only 4V out of spec. Sockets and the like are rated 125V. Electrical gear that is installed in buildings like panels and sockets are made exclusively for the NA market by reputable firms like Leviton and Eaton, often built in China but strictly to American spec. That sea of junk from Alibaba/express/ebay/Amazon fleaMarketplace is not permitted in building wiring because it's not UL listed.
    – Harper
    Dec 4 at 4:54

















up vote
1
down vote

favorite












I've googled this already and found many people saying that Noalox is only for copper to aluminum connections. I know that Noalox stands for "no aluminium oxidation" but brand names often change meaning from their origins over time. I've also seen people claiming their bottle says it is only for aluminum to copper, while other people say their bottle also says it can be used for copper to copper.



Well, my bottle doesn't say anything about aluminium or copper - it just says it can be used for improving and protecting electrical connections.



Since I am replacing some outdoor outlets and switches that are about 20 years old and mostly rusted to hell, I thought it might be a good idea to put some conductive grease on the contacts for longevity's sake. (I am already replacing all outdoor wingnuts with weatherproof wingnuts which I think also have some kind of grease inside).



It seems Noalox is the only thing my local Home Depot carries for this purpose (or the employee is ill informed) and I'm on a tight schedule so I can't wait for something like Penetrox E-8 to arrive. I know there are concerns about Noalox actually potentially reducing connectivity, but my main concerns is simply ambient humidity and condensation causing corrosion in the contacts over time.



My feeling is that Noalox will do a decent job in this regard, and so even if there is a 1-5% cost in connectivity, there is a 100% improvement in anti-corrosive longevity. Am I wrong? Anyone else care to weigh in?



A related side question: is it a crazy idea to use dielectric grease on the prongs of an outdoor device that is essentially permanently installed and will be plugged into an outdoor receptacle, potentially for years on end? Or is there a better grease for this? Or better nothing at all?



I know there are concerns about non-conductive grease in high voltage applications since they might actually reduce conductivity, but considering most devices are designed for 110V and my mains is actually more like 124V, I don't see that being a huge issue. Especially since these outdoor devices aren't high amperage.










share|improve this question









New contributor




Daniel is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.




















  • Most devices are designed for 125V. Mains voltage hasn't been 110 since the war. When power was first marketed to the masses, it was 110V, and naturally, that stuck the way "Xerox" stuck.
    – Harper
    Dec 4 at 3:36










  • Um, most devices are designed for international use, and 125V is not standard the world over (or even where it is, it's not always dependable). Almost every device I've seen is labeled as 110V - 125V, and sometimes only as 110V. And most devices are built with even more tolerance than the label indicates. Similarly, the other main standard is 220V which actually varies in practice from 220V - 240V+.
    – Daniel
    Dec 4 at 4:12












  • I am discussing the context of your question, which is the I
    – Harper
    Dec 4 at 4:21










  • My point is I'd expect 110V would be well within the design specs / tolerances of any modern device, and I'm doubting that dielectric grease would affect the conductivity by that much. I could be wrong about the effect of the grease - I very much doubt I am wrong about acceptable voltage ranges on any given mainstream electrical device. Mains being reliably 125V in America is pretty irrelevant considering the vast majority of electronic components are built in China for a global market, and even American- or European-built devices will also be aiming for global distribution 9 times of 10.
    – Daniel
    Dec 4 at 4:25












  • I'm just trying to say voltage is supposed to be 120V not 110V, so it's only 4V out of spec. Sockets and the like are rated 125V. Electrical gear that is installed in buildings like panels and sockets are made exclusively for the NA market by reputable firms like Leviton and Eaton, often built in China but strictly to American spec. That sea of junk from Alibaba/express/ebay/Amazon fleaMarketplace is not permitted in building wiring because it's not UL listed.
    – Harper
    Dec 4 at 4:54















up vote
1
down vote

favorite









up vote
1
down vote

favorite











I've googled this already and found many people saying that Noalox is only for copper to aluminum connections. I know that Noalox stands for "no aluminium oxidation" but brand names often change meaning from their origins over time. I've also seen people claiming their bottle says it is only for aluminum to copper, while other people say their bottle also says it can be used for copper to copper.



Well, my bottle doesn't say anything about aluminium or copper - it just says it can be used for improving and protecting electrical connections.



Since I am replacing some outdoor outlets and switches that are about 20 years old and mostly rusted to hell, I thought it might be a good idea to put some conductive grease on the contacts for longevity's sake. (I am already replacing all outdoor wingnuts with weatherproof wingnuts which I think also have some kind of grease inside).



It seems Noalox is the only thing my local Home Depot carries for this purpose (or the employee is ill informed) and I'm on a tight schedule so I can't wait for something like Penetrox E-8 to arrive. I know there are concerns about Noalox actually potentially reducing connectivity, but my main concerns is simply ambient humidity and condensation causing corrosion in the contacts over time.



My feeling is that Noalox will do a decent job in this regard, and so even if there is a 1-5% cost in connectivity, there is a 100% improvement in anti-corrosive longevity. Am I wrong? Anyone else care to weigh in?



A related side question: is it a crazy idea to use dielectric grease on the prongs of an outdoor device that is essentially permanently installed and will be plugged into an outdoor receptacle, potentially for years on end? Or is there a better grease for this? Or better nothing at all?



I know there are concerns about non-conductive grease in high voltage applications since they might actually reduce conductivity, but considering most devices are designed for 110V and my mains is actually more like 124V, I don't see that being a huge issue. Especially since these outdoor devices aren't high amperage.










share|improve this question









New contributor




Daniel is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.











I've googled this already and found many people saying that Noalox is only for copper to aluminum connections. I know that Noalox stands for "no aluminium oxidation" but brand names often change meaning from their origins over time. I've also seen people claiming their bottle says it is only for aluminum to copper, while other people say their bottle also says it can be used for copper to copper.



Well, my bottle doesn't say anything about aluminium or copper - it just says it can be used for improving and protecting electrical connections.



Since I am replacing some outdoor outlets and switches that are about 20 years old and mostly rusted to hell, I thought it might be a good idea to put some conductive grease on the contacts for longevity's sake. (I am already replacing all outdoor wingnuts with weatherproof wingnuts which I think also have some kind of grease inside).



It seems Noalox is the only thing my local Home Depot carries for this purpose (or the employee is ill informed) and I'm on a tight schedule so I can't wait for something like Penetrox E-8 to arrive. I know there are concerns about Noalox actually potentially reducing connectivity, but my main concerns is simply ambient humidity and condensation causing corrosion in the contacts over time.



My feeling is that Noalox will do a decent job in this regard, and so even if there is a 1-5% cost in connectivity, there is a 100% improvement in anti-corrosive longevity. Am I wrong? Anyone else care to weigh in?



A related side question: is it a crazy idea to use dielectric grease on the prongs of an outdoor device that is essentially permanently installed and will be plugged into an outdoor receptacle, potentially for years on end? Or is there a better grease for this? Or better nothing at all?



I know there are concerns about non-conductive grease in high voltage applications since they might actually reduce conductivity, but considering most devices are designed for 110V and my mains is actually more like 124V, I don't see that being a huge issue. Especially since these outdoor devices aren't high amperage.







electrical receptacle outdoor corrosion






share|improve this question









New contributor




Daniel is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.











share|improve this question









New contributor




Daniel is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









share|improve this question




share|improve this question








edited Dec 4 at 1:41





















New contributor




Daniel is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









asked Dec 4 at 1:22









Daniel

1363




1363




New contributor




Daniel is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.





New contributor





Daniel is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.






Daniel is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.












  • Most devices are designed for 125V. Mains voltage hasn't been 110 since the war. When power was first marketed to the masses, it was 110V, and naturally, that stuck the way "Xerox" stuck.
    – Harper
    Dec 4 at 3:36










  • Um, most devices are designed for international use, and 125V is not standard the world over (or even where it is, it's not always dependable). Almost every device I've seen is labeled as 110V - 125V, and sometimes only as 110V. And most devices are built with even more tolerance than the label indicates. Similarly, the other main standard is 220V which actually varies in practice from 220V - 240V+.
    – Daniel
    Dec 4 at 4:12












  • I am discussing the context of your question, which is the I
    – Harper
    Dec 4 at 4:21










  • My point is I'd expect 110V would be well within the design specs / tolerances of any modern device, and I'm doubting that dielectric grease would affect the conductivity by that much. I could be wrong about the effect of the grease - I very much doubt I am wrong about acceptable voltage ranges on any given mainstream electrical device. Mains being reliably 125V in America is pretty irrelevant considering the vast majority of electronic components are built in China for a global market, and even American- or European-built devices will also be aiming for global distribution 9 times of 10.
    – Daniel
    Dec 4 at 4:25












  • I'm just trying to say voltage is supposed to be 120V not 110V, so it's only 4V out of spec. Sockets and the like are rated 125V. Electrical gear that is installed in buildings like panels and sockets are made exclusively for the NA market by reputable firms like Leviton and Eaton, often built in China but strictly to American spec. That sea of junk from Alibaba/express/ebay/Amazon fleaMarketplace is not permitted in building wiring because it's not UL listed.
    – Harper
    Dec 4 at 4:54




















  • Most devices are designed for 125V. Mains voltage hasn't been 110 since the war. When power was first marketed to the masses, it was 110V, and naturally, that stuck the way "Xerox" stuck.
    – Harper
    Dec 4 at 3:36










  • Um, most devices are designed for international use, and 125V is not standard the world over (or even where it is, it's not always dependable). Almost every device I've seen is labeled as 110V - 125V, and sometimes only as 110V. And most devices are built with even more tolerance than the label indicates. Similarly, the other main standard is 220V which actually varies in practice from 220V - 240V+.
    – Daniel
    Dec 4 at 4:12












  • I am discussing the context of your question, which is the I
    – Harper
    Dec 4 at 4:21










  • My point is I'd expect 110V would be well within the design specs / tolerances of any modern device, and I'm doubting that dielectric grease would affect the conductivity by that much. I could be wrong about the effect of the grease - I very much doubt I am wrong about acceptable voltage ranges on any given mainstream electrical device. Mains being reliably 125V in America is pretty irrelevant considering the vast majority of electronic components are built in China for a global market, and even American- or European-built devices will also be aiming for global distribution 9 times of 10.
    – Daniel
    Dec 4 at 4:25












  • I'm just trying to say voltage is supposed to be 120V not 110V, so it's only 4V out of spec. Sockets and the like are rated 125V. Electrical gear that is installed in buildings like panels and sockets are made exclusively for the NA market by reputable firms like Leviton and Eaton, often built in China but strictly to American spec. That sea of junk from Alibaba/express/ebay/Amazon fleaMarketplace is not permitted in building wiring because it's not UL listed.
    – Harper
    Dec 4 at 4:54


















Most devices are designed for 125V. Mains voltage hasn't been 110 since the war. When power was first marketed to the masses, it was 110V, and naturally, that stuck the way "Xerox" stuck.
– Harper
Dec 4 at 3:36




Most devices are designed for 125V. Mains voltage hasn't been 110 since the war. When power was first marketed to the masses, it was 110V, and naturally, that stuck the way "Xerox" stuck.
– Harper
Dec 4 at 3:36












Um, most devices are designed for international use, and 125V is not standard the world over (or even where it is, it's not always dependable). Almost every device I've seen is labeled as 110V - 125V, and sometimes only as 110V. And most devices are built with even more tolerance than the label indicates. Similarly, the other main standard is 220V which actually varies in practice from 220V - 240V+.
– Daniel
Dec 4 at 4:12






Um, most devices are designed for international use, and 125V is not standard the world over (or even where it is, it's not always dependable). Almost every device I've seen is labeled as 110V - 125V, and sometimes only as 110V. And most devices are built with even more tolerance than the label indicates. Similarly, the other main standard is 220V which actually varies in practice from 220V - 240V+.
– Daniel
Dec 4 at 4:12














I am discussing the context of your question, which is the I
– Harper
Dec 4 at 4:21




I am discussing the context of your question, which is the I
– Harper
Dec 4 at 4:21












My point is I'd expect 110V would be well within the design specs / tolerances of any modern device, and I'm doubting that dielectric grease would affect the conductivity by that much. I could be wrong about the effect of the grease - I very much doubt I am wrong about acceptable voltage ranges on any given mainstream electrical device. Mains being reliably 125V in America is pretty irrelevant considering the vast majority of electronic components are built in China for a global market, and even American- or European-built devices will also be aiming for global distribution 9 times of 10.
– Daniel
Dec 4 at 4:25






My point is I'd expect 110V would be well within the design specs / tolerances of any modern device, and I'm doubting that dielectric grease would affect the conductivity by that much. I could be wrong about the effect of the grease - I very much doubt I am wrong about acceptable voltage ranges on any given mainstream electrical device. Mains being reliably 125V in America is pretty irrelevant considering the vast majority of electronic components are built in China for a global market, and even American- or European-built devices will also be aiming for global distribution 9 times of 10.
– Daniel
Dec 4 at 4:25














I'm just trying to say voltage is supposed to be 120V not 110V, so it's only 4V out of spec. Sockets and the like are rated 125V. Electrical gear that is installed in buildings like panels and sockets are made exclusively for the NA market by reputable firms like Leviton and Eaton, often built in China but strictly to American spec. That sea of junk from Alibaba/express/ebay/Amazon fleaMarketplace is not permitted in building wiring because it's not UL listed.
– Harper
Dec 4 at 4:54






I'm just trying to say voltage is supposed to be 120V not 110V, so it's only 4V out of spec. Sockets and the like are rated 125V. Electrical gear that is installed in buildings like panels and sockets are made exclusively for the NA market by reputable firms like Leviton and Eaton, often built in China but strictly to American spec. That sea of junk from Alibaba/express/ebay/Amazon fleaMarketplace is not permitted in building wiring because it's not UL listed.
– Harper
Dec 4 at 4:54












2 Answers
2






active

oldest

votes

















up vote
1
down vote













I have used dielectric grease for years in so many applications. For mains voltages is is primarily a non-conductive corrosion barrier. In that sense, any non-conductive grease will do. Electrically, the original metal-to-metal connection is maintained because corrosion is reduced. You can use it liberally around connection points because it does not conduct.

Noalox sems to contain zinc dust in a plastic grease matrix. I'm not sure how conductive it may be at mains voltages, but I would apply it only at the specific connections.






share|improve this answer








New contributor




John Canon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.

























    up vote
    1
    down vote













    Putting aluminum wire on copper terminations is a bad idea, it's what started all the Al hubballoo in the furst place. That is why large lugs are aluminum. Noalox is also for aluminum-aluminum bonding. It will work fine for Cu-Cu. Also, aluminum wireneuts are rubbish.



    You are talking about receptacles that cost 75 cents and wirenuts that cost 3 cents, It isn't worth going to extremes to protect outdoor electrical gear from damage, because that's gonna happen.



    Related, you really want to arrange your wiring so your GFCI protective devices are indoors. You wouldn't leave a phone outdoors and expect it to work for long, don't do that for any other electronic device...






    share|improve this answer





















    • The home is too old and jury-rigged for it to be worth my time to figure out where the wires go and what else is on the circuit and how it is wired. I'm looking to do the best job I can within the limited scope of the assignment. The rest of the circuit can fail for all I care, but the parts that I touch specifically I want to be installed correctly and as reliable for as long as possible. I don't like to get calls later, even years later, for something I should have done right the first time.
      – Daniel
      Dec 4 at 4:09













    Your Answer








    StackExchange.ready(function() {
    var channelOptions = {
    tags: "".split(" "),
    id: "73"
    };
    initTagRenderer("".split(" "), "".split(" "), channelOptions);

    StackExchange.using("externalEditor", function() {
    // Have to fire editor after snippets, if snippets enabled
    if (StackExchange.settings.snippets.snippetsEnabled) {
    StackExchange.using("snippets", function() {
    createEditor();
    });
    }
    else {
    createEditor();
    }
    });

    function createEditor() {
    StackExchange.prepareEditor({
    heartbeatType: 'answer',
    convertImagesToLinks: false,
    noModals: true,
    showLowRepImageUploadWarning: true,
    reputationToPostImages: null,
    bindNavPrevention: true,
    postfix: "",
    imageUploader: {
    brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
    contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
    allowUrls: true
    },
    noCode: true, onDemand: true,
    discardSelector: ".discard-answer"
    ,immediatelyShowMarkdownHelp:true
    });


    }
    });






    Daniel is a new contributor. Be nice, and check out our Code of Conduct.










    draft saved

    draft discarded


















    StackExchange.ready(
    function () {
    StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f151913%2fregarding-greases-for-outdoor-connections-noalox-for-general-use-not-necessari%23new-answer', 'question_page');
    }
    );

    Post as a guest















    Required, but never shown

























    2 Answers
    2






    active

    oldest

    votes








    2 Answers
    2






    active

    oldest

    votes









    active

    oldest

    votes






    active

    oldest

    votes








    up vote
    1
    down vote













    I have used dielectric grease for years in so many applications. For mains voltages is is primarily a non-conductive corrosion barrier. In that sense, any non-conductive grease will do. Electrically, the original metal-to-metal connection is maintained because corrosion is reduced. You can use it liberally around connection points because it does not conduct.

    Noalox sems to contain zinc dust in a plastic grease matrix. I'm not sure how conductive it may be at mains voltages, but I would apply it only at the specific connections.






    share|improve this answer








    New contributor




    John Canon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
    Check out our Code of Conduct.






















      up vote
      1
      down vote













      I have used dielectric grease for years in so many applications. For mains voltages is is primarily a non-conductive corrosion barrier. In that sense, any non-conductive grease will do. Electrically, the original metal-to-metal connection is maintained because corrosion is reduced. You can use it liberally around connection points because it does not conduct.

      Noalox sems to contain zinc dust in a plastic grease matrix. I'm not sure how conductive it may be at mains voltages, but I would apply it only at the specific connections.






      share|improve this answer








      New contributor




      John Canon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
      Check out our Code of Conduct.




















        up vote
        1
        down vote










        up vote
        1
        down vote









        I have used dielectric grease for years in so many applications. For mains voltages is is primarily a non-conductive corrosion barrier. In that sense, any non-conductive grease will do. Electrically, the original metal-to-metal connection is maintained because corrosion is reduced. You can use it liberally around connection points because it does not conduct.

        Noalox sems to contain zinc dust in a plastic grease matrix. I'm not sure how conductive it may be at mains voltages, but I would apply it only at the specific connections.






        share|improve this answer








        New contributor




        John Canon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
        Check out our Code of Conduct.









        I have used dielectric grease for years in so many applications. For mains voltages is is primarily a non-conductive corrosion barrier. In that sense, any non-conductive grease will do. Electrically, the original metal-to-metal connection is maintained because corrosion is reduced. You can use it liberally around connection points because it does not conduct.

        Noalox sems to contain zinc dust in a plastic grease matrix. I'm not sure how conductive it may be at mains voltages, but I would apply it only at the specific connections.







        share|improve this answer








        New contributor




        John Canon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
        Check out our Code of Conduct.









        share|improve this answer



        share|improve this answer






        New contributor




        John Canon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
        Check out our Code of Conduct.









        answered Dec 4 at 2:44









        John Canon

        913




        913




        New contributor




        John Canon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
        Check out our Code of Conduct.





        New contributor





        John Canon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
        Check out our Code of Conduct.






        John Canon is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
        Check out our Code of Conduct.
























            up vote
            1
            down vote













            Putting aluminum wire on copper terminations is a bad idea, it's what started all the Al hubballoo in the furst place. That is why large lugs are aluminum. Noalox is also for aluminum-aluminum bonding. It will work fine for Cu-Cu. Also, aluminum wireneuts are rubbish.



            You are talking about receptacles that cost 75 cents and wirenuts that cost 3 cents, It isn't worth going to extremes to protect outdoor electrical gear from damage, because that's gonna happen.



            Related, you really want to arrange your wiring so your GFCI protective devices are indoors. You wouldn't leave a phone outdoors and expect it to work for long, don't do that for any other electronic device...






            share|improve this answer





















            • The home is too old and jury-rigged for it to be worth my time to figure out where the wires go and what else is on the circuit and how it is wired. I'm looking to do the best job I can within the limited scope of the assignment. The rest of the circuit can fail for all I care, but the parts that I touch specifically I want to be installed correctly and as reliable for as long as possible. I don't like to get calls later, even years later, for something I should have done right the first time.
              – Daniel
              Dec 4 at 4:09

















            up vote
            1
            down vote













            Putting aluminum wire on copper terminations is a bad idea, it's what started all the Al hubballoo in the furst place. That is why large lugs are aluminum. Noalox is also for aluminum-aluminum bonding. It will work fine for Cu-Cu. Also, aluminum wireneuts are rubbish.



            You are talking about receptacles that cost 75 cents and wirenuts that cost 3 cents, It isn't worth going to extremes to protect outdoor electrical gear from damage, because that's gonna happen.



            Related, you really want to arrange your wiring so your GFCI protective devices are indoors. You wouldn't leave a phone outdoors and expect it to work for long, don't do that for any other electronic device...






            share|improve this answer





















            • The home is too old and jury-rigged for it to be worth my time to figure out where the wires go and what else is on the circuit and how it is wired. I'm looking to do the best job I can within the limited scope of the assignment. The rest of the circuit can fail for all I care, but the parts that I touch specifically I want to be installed correctly and as reliable for as long as possible. I don't like to get calls later, even years later, for something I should have done right the first time.
              – Daniel
              Dec 4 at 4:09















            up vote
            1
            down vote










            up vote
            1
            down vote









            Putting aluminum wire on copper terminations is a bad idea, it's what started all the Al hubballoo in the furst place. That is why large lugs are aluminum. Noalox is also for aluminum-aluminum bonding. It will work fine for Cu-Cu. Also, aluminum wireneuts are rubbish.



            You are talking about receptacles that cost 75 cents and wirenuts that cost 3 cents, It isn't worth going to extremes to protect outdoor electrical gear from damage, because that's gonna happen.



            Related, you really want to arrange your wiring so your GFCI protective devices are indoors. You wouldn't leave a phone outdoors and expect it to work for long, don't do that for any other electronic device...






            share|improve this answer












            Putting aluminum wire on copper terminations is a bad idea, it's what started all the Al hubballoo in the furst place. That is why large lugs are aluminum. Noalox is also for aluminum-aluminum bonding. It will work fine for Cu-Cu. Also, aluminum wireneuts are rubbish.



            You are talking about receptacles that cost 75 cents and wirenuts that cost 3 cents, It isn't worth going to extremes to protect outdoor electrical gear from damage, because that's gonna happen.



            Related, you really want to arrange your wiring so your GFCI protective devices are indoors. You wouldn't leave a phone outdoors and expect it to work for long, don't do that for any other electronic device...







            share|improve this answer












            share|improve this answer



            share|improve this answer










            answered Dec 4 at 3:41









            Harper

            63.2k341128




            63.2k341128












            • The home is too old and jury-rigged for it to be worth my time to figure out where the wires go and what else is on the circuit and how it is wired. I'm looking to do the best job I can within the limited scope of the assignment. The rest of the circuit can fail for all I care, but the parts that I touch specifically I want to be installed correctly and as reliable for as long as possible. I don't like to get calls later, even years later, for something I should have done right the first time.
              – Daniel
              Dec 4 at 4:09




















            • The home is too old and jury-rigged for it to be worth my time to figure out where the wires go and what else is on the circuit and how it is wired. I'm looking to do the best job I can within the limited scope of the assignment. The rest of the circuit can fail for all I care, but the parts that I touch specifically I want to be installed correctly and as reliable for as long as possible. I don't like to get calls later, even years later, for something I should have done right the first time.
              – Daniel
              Dec 4 at 4:09


















            The home is too old and jury-rigged for it to be worth my time to figure out where the wires go and what else is on the circuit and how it is wired. I'm looking to do the best job I can within the limited scope of the assignment. The rest of the circuit can fail for all I care, but the parts that I touch specifically I want to be installed correctly and as reliable for as long as possible. I don't like to get calls later, even years later, for something I should have done right the first time.
            – Daniel
            Dec 4 at 4:09






            The home is too old and jury-rigged for it to be worth my time to figure out where the wires go and what else is on the circuit and how it is wired. I'm looking to do the best job I can within the limited scope of the assignment. The rest of the circuit can fail for all I care, but the parts that I touch specifically I want to be installed correctly and as reliable for as long as possible. I don't like to get calls later, even years later, for something I should have done right the first time.
            – Daniel
            Dec 4 at 4:09












            Daniel is a new contributor. Be nice, and check out our Code of Conduct.










            draft saved

            draft discarded


















            Daniel is a new contributor. Be nice, and check out our Code of Conduct.













            Daniel is a new contributor. Be nice, and check out our Code of Conduct.












            Daniel is a new contributor. Be nice, and check out our Code of Conduct.
















            Thanks for contributing an answer to Home Improvement Stack Exchange!


            • Please be sure to answer the question. Provide details and share your research!

            But avoid



            • Asking for help, clarification, or responding to other answers.

            • Making statements based on opinion; back them up with references or personal experience.


            To learn more, see our tips on writing great answers.





            Some of your past answers have not been well-received, and you're in danger of being blocked from answering.


            Please pay close attention to the following guidance:


            • Please be sure to answer the question. Provide details and share your research!

            But avoid



            • Asking for help, clarification, or responding to other answers.

            • Making statements based on opinion; back them up with references or personal experience.


            To learn more, see our tips on writing great answers.




            draft saved


            draft discarded














            StackExchange.ready(
            function () {
            StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f151913%2fregarding-greases-for-outdoor-connections-noalox-for-general-use-not-necessari%23new-answer', 'question_page');
            }
            );

            Post as a guest















            Required, but never shown





















































            Required, but never shown














            Required, but never shown












            Required, but never shown







            Required, but never shown

































            Required, but never shown














            Required, but never shown












            Required, but never shown







            Required, but never shown







            Popular posts from this blog

            數位音樂下載

            When can things happen in Etherscan, such as the picture below?

            格利澤436b