How do I make this wiring inside cabinet safer?





.everyoneloves__top-leaderboard:empty,.everyoneloves__mid-leaderboard:empty,.everyoneloves__bot-mid-leaderboard:empty{ margin-bottom:0;
}







13















tl;dr: How do I make this wiring meet code, or at least safer?



The pic below is inside one of my kitchen cabinets. Once upon a time the stove was located below these cabinets, and that wire must have run to an exhaust fan (note the metal vent in the pic). The stove had been moved to another spot by the time I bought the house, but the wire is still in the cabinet and still live.



When I bought the house the wire (old 2-wire NM, no ground) ran to a light fixture on the underside of the cabinet, but there was no junction box at all. Just exposed pigtails inside the cabinet. I'd like to improve things here, so what can I do, short of running a brand new wire with a ground through the wall? I figure putting the pigtails in an actual junction box would be a good place to start.



I plan on staying in the house for a few more years, so I'm more concerned with safety than exactly meeting code.



enter image description here










share|improve this question









New contributor




BradDaBug is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.
















  • 1





    Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?

    – PhilippNagel
    yesterday






  • 1





    @PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.

    – BradDaBug
    yesterday











  • Are these wires controlled by a switch?

    – Freiheit
    12 hours ago








  • 1





    Since there is no ground, DO NOT use a metal box!

    – Hot Licks
    7 hours ago


















13















tl;dr: How do I make this wiring meet code, or at least safer?



The pic below is inside one of my kitchen cabinets. Once upon a time the stove was located below these cabinets, and that wire must have run to an exhaust fan (note the metal vent in the pic). The stove had been moved to another spot by the time I bought the house, but the wire is still in the cabinet and still live.



When I bought the house the wire (old 2-wire NM, no ground) ran to a light fixture on the underside of the cabinet, but there was no junction box at all. Just exposed pigtails inside the cabinet. I'd like to improve things here, so what can I do, short of running a brand new wire with a ground through the wall? I figure putting the pigtails in an actual junction box would be a good place to start.



I plan on staying in the house for a few more years, so I'm more concerned with safety than exactly meeting code.



enter image description here










share|improve this question









New contributor




BradDaBug is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.
















  • 1





    Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?

    – PhilippNagel
    yesterday






  • 1





    @PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.

    – BradDaBug
    yesterday











  • Are these wires controlled by a switch?

    – Freiheit
    12 hours ago








  • 1





    Since there is no ground, DO NOT use a metal box!

    – Hot Licks
    7 hours ago














13












13








13


1






tl;dr: How do I make this wiring meet code, or at least safer?



The pic below is inside one of my kitchen cabinets. Once upon a time the stove was located below these cabinets, and that wire must have run to an exhaust fan (note the metal vent in the pic). The stove had been moved to another spot by the time I bought the house, but the wire is still in the cabinet and still live.



When I bought the house the wire (old 2-wire NM, no ground) ran to a light fixture on the underside of the cabinet, but there was no junction box at all. Just exposed pigtails inside the cabinet. I'd like to improve things here, so what can I do, short of running a brand new wire with a ground through the wall? I figure putting the pigtails in an actual junction box would be a good place to start.



I plan on staying in the house for a few more years, so I'm more concerned with safety than exactly meeting code.



enter image description here










share|improve this question









New contributor




BradDaBug is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.












tl;dr: How do I make this wiring meet code, or at least safer?



The pic below is inside one of my kitchen cabinets. Once upon a time the stove was located below these cabinets, and that wire must have run to an exhaust fan (note the metal vent in the pic). The stove had been moved to another spot by the time I bought the house, but the wire is still in the cabinet and still live.



When I bought the house the wire (old 2-wire NM, no ground) ran to a light fixture on the underside of the cabinet, but there was no junction box at all. Just exposed pigtails inside the cabinet. I'd like to improve things here, so what can I do, short of running a brand new wire with a ground through the wall? I figure putting the pigtails in an actual junction box would be a good place to start.



I plan on staying in the house for a few more years, so I'm more concerned with safety than exactly meeting code.



enter image description here







electrical wiring






share|improve this question









New contributor




BradDaBug is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.











share|improve this question









New contributor




BradDaBug is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









share|improve this question




share|improve this question








edited 15 hours ago









Machavity

8,43821942




8,43821942






New contributor




BradDaBug is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.









asked yesterday









BradDaBugBradDaBug

16614




16614




New contributor




BradDaBug is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.





New contributor





BradDaBug is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.






BradDaBug is a new contributor to this site. Take care in asking for clarification, commenting, and answering.
Check out our Code of Conduct.








  • 1





    Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?

    – PhilippNagel
    yesterday






  • 1





    @PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.

    – BradDaBug
    yesterday











  • Are these wires controlled by a switch?

    – Freiheit
    12 hours ago








  • 1





    Since there is no ground, DO NOT use a metal box!

    – Hot Licks
    7 hours ago














  • 1





    Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?

    – PhilippNagel
    yesterday






  • 1





    @PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.

    – BradDaBug
    yesterday











  • Are these wires controlled by a switch?

    – Freiheit
    12 hours ago








  • 1





    Since there is no ground, DO NOT use a metal box!

    – Hot Licks
    7 hours ago








1




1





Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?

– PhilippNagel
yesterday





Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?

– PhilippNagel
yesterday




1




1





@PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.

– BradDaBug
yesterday





@PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.

– BradDaBug
yesterday













Are these wires controlled by a switch?

– Freiheit
12 hours ago







Are these wires controlled by a switch?

– Freiheit
12 hours ago






1




1





Since there is no ground, DO NOT use a metal box!

– Hot Licks
7 hours ago





Since there is no ground, DO NOT use a metal box!

– Hot Licks
7 hours ago










5 Answers
5






active

oldest

votes


















13














There is nothing you can do with old wiring that doesn't meet code that will make it meet code. Old NM cable with no ground may have been "grandfathered" into an existing building, so long as you don't alter it. But that would not apply here because the WAY it was done was never per code.



Do you really need a circuit there? I would just find out where it comes from and disconnect it there, then pull it out. If you DO want another circuit there, you can attach new NM cable with a ground to the end of this before pulling it out, then get an "old work box" that can be mounted into the wall properly. An old work box is designed to go into a cut-out in the wall, then has "molly bolt" type fasteners that turn behind the wall and snug up against the back of it to hold the box in place (make sure you put the wire through the KO first!). Once the wire is in there, you can put in a receptacle for a light, fan etc.






share|improve this answer



















  • 6





    If it's stapled anywhere it probably won't pull.

    – J...
    yesterday











  • True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!

    – J. Raefield
    yesterday






  • 4





    Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.

    – J...
    yesterday



















5














Sounds like you don't want the wire.



First figure out which breaker that circuit is on.



Turn off the breaker, see what other things go off. Put a harmonic tracer on the wire, find where it junctions and disconnect it there.



Typically fanhoods are on a circuit with other items. Once you have it disconnected in the box you could cut it back to the knock out and push it through so it could never be energized again then you could cut the wire in the cabinet back to where it penetrates the cabinet.



Or go with your plan put a box with a cover and wire nuts and leave it live.






share|improve this answer































    5














    You may want to find what the local code says about such and follow it. I think just putting it "properly" in a metal box should be sufficient. Be sure the box is secure, the wires is clamped in the box and the caps are left on. As an extra measurement you could even cap them and then run electrical tape around them to ensure the caps won't fall off. Be sure to put a cover over the box when all done. Writing on the cover of what it is can't hurt either. If it is on its own circuit you could even turn the breaker off after this and label in the breaker as well.






    share|improve this answer



















    • 1





      DO NOT use a metal box if there is no ground!

      – Hot Licks
      7 hours ago











    • @HotLicks username appropriate..

      – Alex M
      5 hours ago



















    2














    Meeting your request for safety, and ranked best to worst:




    1. Trip and remove the breaker, replacing it with an appropriate position plug (other circuits may be on the breaker, preventing this).


    2. Disconnect the wire from wherever it goes (the breaker, an outlet, etc.) and pull it out (it may be stapled, preventing this).


    3. (After temporarily tripping breaker): Thread wire into a junction box with a stress-relief connector. Position the box as close to the hole in the wall as possible. Re-cap the wires, wrap with electrical tape. Screw to the wall and affix face plate.


    4. (After temporarily tripping breaker): Wrap a few turns around the wire nuts with electrical tape, then wrap the entire NM from where the outer insulation was stripped away to and including the wire nuts.



    As others have mentioned, there isn't a code-happy solution here. However, solutions (1)-(3) will pass a home inspection when you sell the home. (4) might not. It will depend on the inspector.






    share|improve this answer





















    • 2





      (4) is certain to alarm the inspector if you wrap with 'electrical wire' instead of electrical tape ;)

      – amI
      11 hours ago






    • 1





      @amI THANK YOU! Imperfection is sooo inconvenient. :-)

      – JBH
      9 hours ago



















    0














    Trace these wires back to where they are spliced on the branched and disconnect. Remove if possible and plug holes at boxes or panels where this wire ran.






    share|improve this answer
























      Your Answer








      StackExchange.ready(function() {
      var channelOptions = {
      tags: "".split(" "),
      id: "73"
      };
      initTagRenderer("".split(" "), "".split(" "), channelOptions);

      StackExchange.using("externalEditor", function() {
      // Have to fire editor after snippets, if snippets enabled
      if (StackExchange.settings.snippets.snippetsEnabled) {
      StackExchange.using("snippets", function() {
      createEditor();
      });
      }
      else {
      createEditor();
      }
      });

      function createEditor() {
      StackExchange.prepareEditor({
      heartbeatType: 'answer',
      autoActivateHeartbeat: false,
      convertImagesToLinks: false,
      noModals: true,
      showLowRepImageUploadWarning: true,
      reputationToPostImages: null,
      bindNavPrevention: true,
      postfix: "",
      imageUploader: {
      brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
      contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
      allowUrls: true
      },
      noCode: true, onDemand: true,
      discardSelector: ".discard-answer"
      ,immediatelyShowMarkdownHelp:true
      });


      }
      });






      BradDaBug is a new contributor. Be nice, and check out our Code of Conduct.










      draft saved

      draft discarded


















      StackExchange.ready(
      function () {
      StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f162263%2fhow-do-i-make-this-wiring-inside-cabinet-safer%23new-answer', 'question_page');
      }
      );

      Post as a guest















      Required, but never shown

























      5 Answers
      5






      active

      oldest

      votes








      5 Answers
      5






      active

      oldest

      votes









      active

      oldest

      votes






      active

      oldest

      votes









      13














      There is nothing you can do with old wiring that doesn't meet code that will make it meet code. Old NM cable with no ground may have been "grandfathered" into an existing building, so long as you don't alter it. But that would not apply here because the WAY it was done was never per code.



      Do you really need a circuit there? I would just find out where it comes from and disconnect it there, then pull it out. If you DO want another circuit there, you can attach new NM cable with a ground to the end of this before pulling it out, then get an "old work box" that can be mounted into the wall properly. An old work box is designed to go into a cut-out in the wall, then has "molly bolt" type fasteners that turn behind the wall and snug up against the back of it to hold the box in place (make sure you put the wire through the KO first!). Once the wire is in there, you can put in a receptacle for a light, fan etc.






      share|improve this answer



















      • 6





        If it's stapled anywhere it probably won't pull.

        – J...
        yesterday











      • True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!

        – J. Raefield
        yesterday






      • 4





        Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.

        – J...
        yesterday
















      13














      There is nothing you can do with old wiring that doesn't meet code that will make it meet code. Old NM cable with no ground may have been "grandfathered" into an existing building, so long as you don't alter it. But that would not apply here because the WAY it was done was never per code.



      Do you really need a circuit there? I would just find out where it comes from and disconnect it there, then pull it out. If you DO want another circuit there, you can attach new NM cable with a ground to the end of this before pulling it out, then get an "old work box" that can be mounted into the wall properly. An old work box is designed to go into a cut-out in the wall, then has "molly bolt" type fasteners that turn behind the wall and snug up against the back of it to hold the box in place (make sure you put the wire through the KO first!). Once the wire is in there, you can put in a receptacle for a light, fan etc.






      share|improve this answer



















      • 6





        If it's stapled anywhere it probably won't pull.

        – J...
        yesterday











      • True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!

        – J. Raefield
        yesterday






      • 4





        Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.

        – J...
        yesterday














      13












      13








      13







      There is nothing you can do with old wiring that doesn't meet code that will make it meet code. Old NM cable with no ground may have been "grandfathered" into an existing building, so long as you don't alter it. But that would not apply here because the WAY it was done was never per code.



      Do you really need a circuit there? I would just find out where it comes from and disconnect it there, then pull it out. If you DO want another circuit there, you can attach new NM cable with a ground to the end of this before pulling it out, then get an "old work box" that can be mounted into the wall properly. An old work box is designed to go into a cut-out in the wall, then has "molly bolt" type fasteners that turn behind the wall and snug up against the back of it to hold the box in place (make sure you put the wire through the KO first!). Once the wire is in there, you can put in a receptacle for a light, fan etc.






      share|improve this answer













      There is nothing you can do with old wiring that doesn't meet code that will make it meet code. Old NM cable with no ground may have been "grandfathered" into an existing building, so long as you don't alter it. But that would not apply here because the WAY it was done was never per code.



      Do you really need a circuit there? I would just find out where it comes from and disconnect it there, then pull it out. If you DO want another circuit there, you can attach new NM cable with a ground to the end of this before pulling it out, then get an "old work box" that can be mounted into the wall properly. An old work box is designed to go into a cut-out in the wall, then has "molly bolt" type fasteners that turn behind the wall and snug up against the back of it to hold the box in place (make sure you put the wire through the KO first!). Once the wire is in there, you can put in a receptacle for a light, fan etc.







      share|improve this answer












      share|improve this answer



      share|improve this answer










      answered yesterday









      J. RaefieldJ. Raefield

      4,034211




      4,034211








      • 6





        If it's stapled anywhere it probably won't pull.

        – J...
        yesterday











      • True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!

        – J. Raefield
        yesterday






      • 4





        Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.

        – J...
        yesterday














      • 6





        If it's stapled anywhere it probably won't pull.

        – J...
        yesterday











      • True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!

        – J. Raefield
        yesterday






      • 4





        Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.

        – J...
        yesterday








      6




      6





      If it's stapled anywhere it probably won't pull.

      – J...
      yesterday





      If it's stapled anywhere it probably won't pull.

      – J...
      yesterday













      True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!

      – J. Raefield
      yesterday





      True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!

      – J. Raefield
      yesterday




      4




      4





      Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.

      – J...
      yesterday





      Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.

      – J...
      yesterday













      5














      Sounds like you don't want the wire.



      First figure out which breaker that circuit is on.



      Turn off the breaker, see what other things go off. Put a harmonic tracer on the wire, find where it junctions and disconnect it there.



      Typically fanhoods are on a circuit with other items. Once you have it disconnected in the box you could cut it back to the knock out and push it through so it could never be energized again then you could cut the wire in the cabinet back to where it penetrates the cabinet.



      Or go with your plan put a box with a cover and wire nuts and leave it live.






      share|improve this answer




























        5














        Sounds like you don't want the wire.



        First figure out which breaker that circuit is on.



        Turn off the breaker, see what other things go off. Put a harmonic tracer on the wire, find where it junctions and disconnect it there.



        Typically fanhoods are on a circuit with other items. Once you have it disconnected in the box you could cut it back to the knock out and push it through so it could never be energized again then you could cut the wire in the cabinet back to where it penetrates the cabinet.



        Or go with your plan put a box with a cover and wire nuts and leave it live.






        share|improve this answer


























          5












          5








          5







          Sounds like you don't want the wire.



          First figure out which breaker that circuit is on.



          Turn off the breaker, see what other things go off. Put a harmonic tracer on the wire, find where it junctions and disconnect it there.



          Typically fanhoods are on a circuit with other items. Once you have it disconnected in the box you could cut it back to the knock out and push it through so it could never be energized again then you could cut the wire in the cabinet back to where it penetrates the cabinet.



          Or go with your plan put a box with a cover and wire nuts and leave it live.






          share|improve this answer













          Sounds like you don't want the wire.



          First figure out which breaker that circuit is on.



          Turn off the breaker, see what other things go off. Put a harmonic tracer on the wire, find where it junctions and disconnect it there.



          Typically fanhoods are on a circuit with other items. Once you have it disconnected in the box you could cut it back to the knock out and push it through so it could never be energized again then you could cut the wire in the cabinet back to where it penetrates the cabinet.



          Or go with your plan put a box with a cover and wire nuts and leave it live.







          share|improve this answer












          share|improve this answer



          share|improve this answer










          answered yesterday









          Fresh CodemongerFresh Codemonger

          5117




          5117























              5














              You may want to find what the local code says about such and follow it. I think just putting it "properly" in a metal box should be sufficient. Be sure the box is secure, the wires is clamped in the box and the caps are left on. As an extra measurement you could even cap them and then run electrical tape around them to ensure the caps won't fall off. Be sure to put a cover over the box when all done. Writing on the cover of what it is can't hurt either. If it is on its own circuit you could even turn the breaker off after this and label in the breaker as well.






              share|improve this answer



















              • 1





                DO NOT use a metal box if there is no ground!

                – Hot Licks
                7 hours ago











              • @HotLicks username appropriate..

                – Alex M
                5 hours ago
















              5














              You may want to find what the local code says about such and follow it. I think just putting it "properly" in a metal box should be sufficient. Be sure the box is secure, the wires is clamped in the box and the caps are left on. As an extra measurement you could even cap them and then run electrical tape around them to ensure the caps won't fall off. Be sure to put a cover over the box when all done. Writing on the cover of what it is can't hurt either. If it is on its own circuit you could even turn the breaker off after this and label in the breaker as well.






              share|improve this answer



















              • 1





                DO NOT use a metal box if there is no ground!

                – Hot Licks
                7 hours ago











              • @HotLicks username appropriate..

                – Alex M
                5 hours ago














              5












              5








              5







              You may want to find what the local code says about such and follow it. I think just putting it "properly" in a metal box should be sufficient. Be sure the box is secure, the wires is clamped in the box and the caps are left on. As an extra measurement you could even cap them and then run electrical tape around them to ensure the caps won't fall off. Be sure to put a cover over the box when all done. Writing on the cover of what it is can't hurt either. If it is on its own circuit you could even turn the breaker off after this and label in the breaker as well.






              share|improve this answer













              You may want to find what the local code says about such and follow it. I think just putting it "properly" in a metal box should be sufficient. Be sure the box is secure, the wires is clamped in the box and the caps are left on. As an extra measurement you could even cap them and then run electrical tape around them to ensure the caps won't fall off. Be sure to put a cover over the box when all done. Writing on the cover of what it is can't hurt either. If it is on its own circuit you could even turn the breaker off after this and label in the breaker as well.







              share|improve this answer












              share|improve this answer



              share|improve this answer










              answered yesterday









              Micah MontoyaMicah Montoya

              61916




              61916








              • 1





                DO NOT use a metal box if there is no ground!

                – Hot Licks
                7 hours ago











              • @HotLicks username appropriate..

                – Alex M
                5 hours ago














              • 1





                DO NOT use a metal box if there is no ground!

                – Hot Licks
                7 hours ago











              • @HotLicks username appropriate..

                – Alex M
                5 hours ago








              1




              1





              DO NOT use a metal box if there is no ground!

              – Hot Licks
              7 hours ago





              DO NOT use a metal box if there is no ground!

              – Hot Licks
              7 hours ago













              @HotLicks username appropriate..

              – Alex M
              5 hours ago





              @HotLicks username appropriate..

              – Alex M
              5 hours ago











              2














              Meeting your request for safety, and ranked best to worst:




              1. Trip and remove the breaker, replacing it with an appropriate position plug (other circuits may be on the breaker, preventing this).


              2. Disconnect the wire from wherever it goes (the breaker, an outlet, etc.) and pull it out (it may be stapled, preventing this).


              3. (After temporarily tripping breaker): Thread wire into a junction box with a stress-relief connector. Position the box as close to the hole in the wall as possible. Re-cap the wires, wrap with electrical tape. Screw to the wall and affix face plate.


              4. (After temporarily tripping breaker): Wrap a few turns around the wire nuts with electrical tape, then wrap the entire NM from where the outer insulation was stripped away to and including the wire nuts.



              As others have mentioned, there isn't a code-happy solution here. However, solutions (1)-(3) will pass a home inspection when you sell the home. (4) might not. It will depend on the inspector.






              share|improve this answer





















              • 2





                (4) is certain to alarm the inspector if you wrap with 'electrical wire' instead of electrical tape ;)

                – amI
                11 hours ago






              • 1





                @amI THANK YOU! Imperfection is sooo inconvenient. :-)

                – JBH
                9 hours ago
















              2














              Meeting your request for safety, and ranked best to worst:




              1. Trip and remove the breaker, replacing it with an appropriate position plug (other circuits may be on the breaker, preventing this).


              2. Disconnect the wire from wherever it goes (the breaker, an outlet, etc.) and pull it out (it may be stapled, preventing this).


              3. (After temporarily tripping breaker): Thread wire into a junction box with a stress-relief connector. Position the box as close to the hole in the wall as possible. Re-cap the wires, wrap with electrical tape. Screw to the wall and affix face plate.


              4. (After temporarily tripping breaker): Wrap a few turns around the wire nuts with electrical tape, then wrap the entire NM from where the outer insulation was stripped away to and including the wire nuts.



              As others have mentioned, there isn't a code-happy solution here. However, solutions (1)-(3) will pass a home inspection when you sell the home. (4) might not. It will depend on the inspector.






              share|improve this answer





















              • 2





                (4) is certain to alarm the inspector if you wrap with 'electrical wire' instead of electrical tape ;)

                – amI
                11 hours ago






              • 1





                @amI THANK YOU! Imperfection is sooo inconvenient. :-)

                – JBH
                9 hours ago














              2












              2








              2







              Meeting your request for safety, and ranked best to worst:




              1. Trip and remove the breaker, replacing it with an appropriate position plug (other circuits may be on the breaker, preventing this).


              2. Disconnect the wire from wherever it goes (the breaker, an outlet, etc.) and pull it out (it may be stapled, preventing this).


              3. (After temporarily tripping breaker): Thread wire into a junction box with a stress-relief connector. Position the box as close to the hole in the wall as possible. Re-cap the wires, wrap with electrical tape. Screw to the wall and affix face plate.


              4. (After temporarily tripping breaker): Wrap a few turns around the wire nuts with electrical tape, then wrap the entire NM from where the outer insulation was stripped away to and including the wire nuts.



              As others have mentioned, there isn't a code-happy solution here. However, solutions (1)-(3) will pass a home inspection when you sell the home. (4) might not. It will depend on the inspector.






              share|improve this answer















              Meeting your request for safety, and ranked best to worst:




              1. Trip and remove the breaker, replacing it with an appropriate position plug (other circuits may be on the breaker, preventing this).


              2. Disconnect the wire from wherever it goes (the breaker, an outlet, etc.) and pull it out (it may be stapled, preventing this).


              3. (After temporarily tripping breaker): Thread wire into a junction box with a stress-relief connector. Position the box as close to the hole in the wall as possible. Re-cap the wires, wrap with electrical tape. Screw to the wall and affix face plate.


              4. (After temporarily tripping breaker): Wrap a few turns around the wire nuts with electrical tape, then wrap the entire NM from where the outer insulation was stripped away to and including the wire nuts.



              As others have mentioned, there isn't a code-happy solution here. However, solutions (1)-(3) will pass a home inspection when you sell the home. (4) might not. It will depend on the inspector.







              share|improve this answer














              share|improve this answer



              share|improve this answer








              edited 9 hours ago

























              answered yesterday









              JBHJBH

              27529




              27529








              • 2





                (4) is certain to alarm the inspector if you wrap with 'electrical wire' instead of electrical tape ;)

                – amI
                11 hours ago






              • 1





                @amI THANK YOU! Imperfection is sooo inconvenient. :-)

                – JBH
                9 hours ago














              • 2





                (4) is certain to alarm the inspector if you wrap with 'electrical wire' instead of electrical tape ;)

                – amI
                11 hours ago






              • 1





                @amI THANK YOU! Imperfection is sooo inconvenient. :-)

                – JBH
                9 hours ago








              2




              2





              (4) is certain to alarm the inspector if you wrap with 'electrical wire' instead of electrical tape ;)

              – amI
              11 hours ago





              (4) is certain to alarm the inspector if you wrap with 'electrical wire' instead of electrical tape ;)

              – amI
              11 hours ago




              1




              1





              @amI THANK YOU! Imperfection is sooo inconvenient. :-)

              – JBH
              9 hours ago





              @amI THANK YOU! Imperfection is sooo inconvenient. :-)

              – JBH
              9 hours ago











              0














              Trace these wires back to where they are spliced on the branched and disconnect. Remove if possible and plug holes at boxes or panels where this wire ran.






              share|improve this answer




























                0














                Trace these wires back to where they are spliced on the branched and disconnect. Remove if possible and plug holes at boxes or panels where this wire ran.






                share|improve this answer


























                  0












                  0








                  0







                  Trace these wires back to where they are spliced on the branched and disconnect. Remove if possible and plug holes at boxes or panels where this wire ran.






                  share|improve this answer













                  Trace these wires back to where they are spliced on the branched and disconnect. Remove if possible and plug holes at boxes or panels where this wire ran.







                  share|improve this answer












                  share|improve this answer



                  share|improve this answer










                  answered 19 hours ago









                  GeraldGerald

                  271




                  271






















                      BradDaBug is a new contributor. Be nice, and check out our Code of Conduct.










                      draft saved

                      draft discarded


















                      BradDaBug is a new contributor. Be nice, and check out our Code of Conduct.













                      BradDaBug is a new contributor. Be nice, and check out our Code of Conduct.












                      BradDaBug is a new contributor. Be nice, and check out our Code of Conduct.
















                      Thanks for contributing an answer to Home Improvement Stack Exchange!


                      • Please be sure to answer the question. Provide details and share your research!

                      But avoid



                      • Asking for help, clarification, or responding to other answers.

                      • Making statements based on opinion; back them up with references or personal experience.


                      To learn more, see our tips on writing great answers.




                      draft saved


                      draft discarded














                      StackExchange.ready(
                      function () {
                      StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f162263%2fhow-do-i-make-this-wiring-inside-cabinet-safer%23new-answer', 'question_page');
                      }
                      );

                      Post as a guest















                      Required, but never shown





















































                      Required, but never shown














                      Required, but never shown












                      Required, but never shown







                      Required, but never shown

































                      Required, but never shown














                      Required, but never shown












                      Required, but never shown







                      Required, but never shown







                      Popular posts from this blog

                      數位音樂下載

                      When can things happen in Etherscan, such as the picture below?

                      格利澤436b